PAR
Name / SUB xxx: Name
Default setting
Setting range
Address
SUB
004
: Power cycles
-
- (Read only)
0x2D81:004
SUB
005
: Relay cycles
-
- (Read only)
0x2D81:005
SUB
006
: Short-circ. counter
-
- (Read only)
0x2D81:006
SUB
007
: Earth fault counter
-
- (Read only)
0x2D81:007
SUB
008
: Clamp active
-
- (Read only)
0x2D81:008
SUB
009
: Fan oper. time
x s
- (Read only)
0x2D81:009
PAR 155
Fault memory
SUB
000
: Keypad display
-
- (Read only)
0x2006:000
PAR 190
SUB
001
: Product code
-
- (Read only)
0x2000:001
SUB
002
: Serial number
-
- (Read only)
0x2000:002
SUB
004
: CU firmware ver.
-
- (Read only)
0x2000:004
SUB
005
: CU firmware type
-
- (Read only)
0x2000:005
SUB
006
: CU bootlder ver.
-
- (Read only)
0x2000:006
SUB
007
: CU bootlder type
-
- (Read only)
0x2000:007
SUB
008
: OBD version
-
- (Read only)
0x2000:008
SUB
010
: PU firmware ver.
-
- (Read only)
0x2000:010
SUB
011
: PU firmware type
-
- (Read only)
0x2000:011
SUB
012
: PU bootlder ver.
-
- (Read only)
0x2000:012
SUB
013
: PU bootlder type
-
- (Read only)
0x2000:013
PAR 191
Device name
My Device
Text
0x2001
PAR 197
Protection status
-
- (Read only)
0x2040
PAR 198
Status of load. par
-
- (Read only)
0x2827
PAR 200
Control source
Terminal mode [0]
Selection list
0x2824
PAR 201
Standard setpoint
SUB
001
: Frequency setp.
Analog input 1 [2]
Selection list
0x2860:001
SUB
002
: PID setpoint
Keyp.PID.setp. [1]
Selection list
0x2860:002
SUB
003
: Torque setp.
Analog input 1 [2]
Selection list
0x2860:003
PAR 202
Keypad setpoints
SUB
001
: KP freq. setp.
20.0 Hz
0.0 ... 599.0 Hz
0x2601:001
SUB
002
: KP PID setp.
0.00 PUnit
-300.00 ... 300.00 PUnit
0x2601:002
PAR 203
Start/stop confg
SUB
001
: Start method
Normal [0]
Selection list
0x2838:001
SUB
002
: Start at switch-on
OFF [0]
Selection list
0x2838:002
SUB
003
: Stop method
Standard Ramp [1]
Selection list
0x2838:003
PAR 208
Mains volt. sett.
SUB
001
: AC input volt.
230 Veff [0]
Selection list
0x2540:001
SUB
002
: LU warning level
0 V *
0 ... 800 V
0x2540:002
SUB
003
: LU error level
x V
- (Read only)
0x2540:003
SUB
004
: LU deletion level
x V
- (Read only)
0x2540:004
SUB
005
: OU warning level
0 V *
0 ... 800 V
0x2540:005
SUB
006
: OU error level
x V
- (Read only)
0x2540:006
SUB
007
: OU deletion level
x V
- (Read only)
0x2540:007
PAR 210
Min. frequency
0.0 Hz
0.0 ... 599.0 Hz
0x2915
PAR 211
Max. frequency
50.0 Hz
0.0 ... 599.0 Hz
0x2916
PAR 220
Acceleration time 1
5.0 s
0.0 ... 3600.0 s
0x2917
PAR 221
Deceleration time 1
5.0 s
0.0 ... 3600.0 s
0x2918
PAR 222
Acceleration time 2
5.0 s
0.0 ... 3600.0 s
0x2919
PAR 223
Deceleration time 2
5.0 s
0.0 ... 3600.0 s
0x291A
PAR 224
Switch ramp
0.0 Hz
0.0 ... 599.0 Hz
0x291B
PAR 225
QSP dec. time
1.0 s
0.0 ... 3600.0 s
0x291C
PAR 226
S-ramp char.
SUB
001
: S-Ramp smoothing
0.0 %
0.0 ... 100.0 %
0x291E:001
* Default setting depending on the size.
Firmware-Version 01.01.01.00
Commissioning
Keypad parameter list
26