Parameter
Name / value range / [default setting]
Info
Bit 5 Speed 2 limited
1 ≡ input of speed controller 2 in torque mode in limitation.
Bit 6 Upper speed limit active
1 ≡ speed is limited to upper speed limit in torque mode .
Bit 7 Lower speed limit active
1 ≡ speed is limited to lower speed limit in torque mode .
Bit 8 Reserved
-
Bit 9
Bit 10 Output frequency limited
1 ≡ setpoint frequency with V/f operation in limitation.
Bit 11 Magnetisation completed
1 ≡ during V/f operation, the factor 7 rotor time constant has passed
(calculated from the time at which the inverter was enabled without
restart on the fly and with a total motor current of 20 % rated motor cur-
rent for the first time). Otherwise 0.
Bit 12 Motor phase error
1 ≡ motor phase failure detection active.
Bit 13 Reserved
-
Bit 14 Blocking time for error reset is active
1 ≡ the fault can only be reset when the blocking time has elapsed.
Bit 15 Reserved
-
0x2833
Lenze status word 2
•
Read only
Bit-coded Lenze status word.
Bit 0 Reserved
-
Bit 1 Manual test mode active
1 ≡ manual test mode active.
Bit 2 Manual control active
1 ≡ manual control active.
Bit 3 Reserved
-
Bit 4
Bit 5
Bit 6 DC braking active
1 ≡ DC braking active.
Bit 7 Reserved
-
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
0x2DAC
(PAR 119)
Keypad status
(Keypad status)
•
Read only
Bit-coded display of the keypad status.
Bit 0 Start Key
1 ≡ keypad key activated.
Bit 1 Stop Key
Bit 2 Up arrow
Bit 3 Down arrow
Bit 4 Enter Key
Bit 5 Back key
Bit 6 Reserved
-
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
0x2DAD
(PAR 120)
Internal hardware states
(Int. HW states)
•
Read only
Bit-coded display of internal hardware states.
Bit 0 Relay
0 ≡ X9/NO-COM open and NC-COM closed.
1 ≡ X9/NO-COM closed and NC-COM open.
Diagnostics and fault elimination
Diagnostics
Inverter diagnostics
52