Parameter
Name / value range / [default setting]
Info
0x2838:001
(PAR 203/001)
Start/stop configuration: Start method
(Start/stop confg: Start method)
•
Setting can only be changed if controller inhibit is
active.
Starting performance of the inverter.
0 Normal
After switch-on, the standard ramps are active.
•
Acceleration time 1 can be set in
0x2917 (PAR 220)
.
•
Deceleration time 1 can be set in
0x2918 (PAR 221)
.
1 Start with DC braking
After switch-on, the "DC braking" function is active for the time set in
0x2B84:002 (PAR 704/002)
.
4
DC braking
^
153
2 Flying Start
After switch-on, the "Restart on the fly" function is active.
This function makes it possible to restart a coasting motor on the fly dur-
ing operation without speed feedback. Synchronicity between the inver-
ter and the motor is coordinated so that the transition to the rotating
drive is effected without jerk at the time of connection.
4
Flying restart function
^
182
0x2838:003
(PAR 203/003)
Start/stop configuration: Stop method
(Start/stop confg: Stop method)
Behaviour after the "Stop" command.
0 Coasting
The motor coasts down to standstill.
1 Standard Ramp
The motor is brought to a standstill with deceleration time 1 (or deceler-
ation time 2, if activated).
•
Deceleration time 1 can be set in
0x2918 (PAR 221)
.
•
Deceleration time 2 can be set in
0x291A (PAR 223)
.
4
Frequency limits and ramp times
^
73
2 Quick stop ramp
The motor is brought to a standstill with the deceleration time set for
the "Quick stop" function.
•
Deceleration time for quick stop can be set in
0x291C (PAR 225)
.
Additional functions
DC braking