Parameter
Name / value range / [default setting]
Info
1 Analog input 1
2 Analog input 2
3 Keypad Setpoint
4 Digital frequency via DIx
Frequency setpoint at digital input 1.
5 Network Setpoint
11 Preset setpoint 1
Preset values 1 … 15
12 Preset setpoint 2
13 Preset setpoint 3
14 Preset setpoint 4
15 Preset setpoint 5
16 Preset setpoint 6
17 Preset setpoint 7
18 Preset setpoint 8
19 Preset setpoint 9
20 Preset setpoint 10
21 Preset setpoint 11
22 Preset setpoint 12
23 Preset setpoint 13
24 Preset setpoint 14
25 Preset setpoint 15
31 Preset segm. val. 1
"Sequencer" function
32 Preset segm. val. 2
33 Preset segm. val. 3
34 Preset segm. val. 4
35 Preset segm. val. 5
36 Preset segm. val. 6
37 Preset segm. val. 7
38 Preset segm. val. 8
39 Last segment
50 Motor potentiometer
"Motor potentiometer" function
99 Test setpoint
0x282B:003
(PAR 125/003)
Inverter diagnostics: Keypad LCD status
(Inverter diag.: LCD icon status)
•
Read only
Bit-coded state of the keypad status displays.
Bit 0 LOC
1 ≡ local keypad control active.
Bit 1 REM
1 ≡ remote control via terminals, network, etc. active.
Bit 2 MAN
1 ≡ manual setpoint selection via keypad active.
Bit 3 Auto
1 ≡ automatic setpoint selection via terminals, network, etc. active.
Bit 4 Set
Bit 5 Reserved
-
Bit 6
Bit 7
0x282B:004
(PAR 125/004)
Inverter diagnostics: Active drive mode
(Inverter diag.: Drive mode)
•
Read only
Display of the active drive mode.
0 Speed mode
Speed mode active.
1 Process controller mode
Process controller mode active.
3 Test mode (internal)
Test mode active.
4 Jog operation
"Foward jog (CW)" or "Backward jog (CCW)" function active.
0x2831
Lenze status word
•
Read only
Bit-coded status word of the internal motor control.
Bit 0 Reserved
-
Bit 1 Speed 1 limited
1 ≡ input of speed controller 1 in limitation.
Bit 2 Speed limited
1 ≡ output of speed controller 1 in limitation.
Bit 3 Torque limited
1 ≡ setpoint torque in limitation.
Bit 4 Current limited
1 ≡ setpoint current in limitation.
Diagnostics and fault elimination
Diagnostics
Inverter diagnostics
51