Address
Name / Subindex: Name
Default setting
Setting range
D / F / A / M
005
: PDO1 transmitted
-
- (Read only)
U16 / 1 / - / -
006
: PDO2 transmitted
-
- (Read only)
U16 / 1 / - / -
007
: PDO3 transmitted
-
- (Read only)
U16 / 1 / - / -
009
: SDO1 telegrams
-
- (Read only)
U16 / 1 / - / -
010
: SDO2 telegrams
-
- (Read only)
U16 / 1 / - / -
0x230B
CANopen error counter
-
- (Read only)
U16 / 1 / - / -
0x231F
Module ID
001
: Active module ID
-
- (Read only)
U8 / 1 / P / -
002
: Module ID connected
-
- (Read only)
U8 / 1 / - / -
0x2320
Activate Modbus network
0
0 ... 1
U8 / 1 / X / -
0x2321
Modbus settings
001
: Node ID
1
1 ... 247
U8 / 1 / P / -
002
: Baud rate
Automatic [0]
Selection list
U8 / 1 / P / -
003
: Data format
Automatic [0]
Selection list
U8 / 1 / P / -
004
: Minimum response time
0 ms
0 ... 1000 ms
U16 / 1 / P / -
0x2322
Active Modbus settings
001
: Node ID
-
- (Read only)
U8 / 1 / X / -
002
: Baud rate
-
- (Read only)
U8 / 1 / X / -
003
: Data format
-
- (Read only)
U8 / 1 / X / -
0x2323
DIP switch position
-
- (Read only)
U16 / 1 / - / -
0x232A
Modbus statistics
001
: Messages received
-
- (Read only)
U32 / 1 / X / -
002
: Valid messages received
-
- (Read only)
U32 / 1 / X / -
003
: Messages with exceptions
-
- (Read only)
U32 / 1 / X / -
004
: Messages with errors
-
- (Read only)
U32 / 1 / X / -
005
: Messages sent
-
- (Read only)
U32 / 1 / X / -
0x232B
Modbus parameter mapping
001
: Parameter 1
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
002
: Parameter 2
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
003
: Parameter 3
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
004
: Parameter 4
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
005
: Parameter 5
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
006
: Parameter 6
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
007
: Parameter 7
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
008
: Parameter 8
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
009
: Parameter 9
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
010
: Parameter 10
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
011
: Parameter 11
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
012
: Parameter 12
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
013
: Parameter 13
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
014
: Parameter 14
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
015
: Parameter 15
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
016
: Parameter 16
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
017
: Parameter 17
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
018
: Parameter 18
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
019
: Parameter 19
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
020
: Parameter 20
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
021
: Parameter 21
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
022
: Parameter 22
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
023
: Parameter 23
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
024
: Parameter 24
0x00000000
0x00000000 ... 0xFFFFFF00
L_INDEX / 1 / PH / -
0x232C
Modbus register assignment
001
: Register 1
-
- (Read only)
U16 / 1 / - / -
002
: Register 2
-
- (Read only)
U16 / 1 / - / -
* Default setting depending on the size.
Firmware-Version 01.01.01.00
Appendix
Parameter attribute list
234