10.7
Favorites
In order to gain quick access using »EASY Starter« or the keypad, frequently used parameters
of the inverter can be defined as "Favorites".
•
»EASY Starter« provides quick access to the "Favorites" via the Favorites tab.
•
On the keypad, the "Favorites" can be found in group 0.
10.7.1
Accessing the "Favorites" with the keypad
S T O P
MAN
AUTO SET
LOC
REM
5 0
MAN
AUTO SET
LOC
REM
P220/000
G R O U P 0
MAN
AUTO SET
LOC
REM
Favorites
P 1 0 0 o o
MAN
AUTO SET
LOC
REM
Actual frequency
8 0
MAN
AUTO SET
LOC
REM
P220/000
1.
2.
3.
4.
5.
6.
VEL:FLEX:AIN1
s
s
P 2 2 0 o o
MAN
AUTO SET
LOC
REM
Accel time 1
1. Use the key in the operating mode to navigate to the
parameterisation mode one level below.
You are now in the group level. All parameters of the
inverter are divided into different groups according to
their function.
Group 0 contains the "Favorites".
Note: By using the key you can navigate one level
upwards again anytime.
2. Use the key to navigate to one level below.
You are now in the parameter level of the group selec-
ted.
3. Use the and navigation keys to select the desired
parameter.
4. Use the key to navigate to one level below.
You are now in the editing mode.
5. Set the desired value using the and navigation
keys.
6. Use the key to accept the changed setting.
The editing mode is exited.
Note: By using the key you can exit the editing mode
without accepting the new setting (abort).
10.7.2
Favorites parameter list (default setting)
In the default setting, the most common parameters for the solution of typical applications
are defined as "Favorites":
No.
Display
Name
Default setting
Setting range
Info
1
P100.00
Actual frequency
x.x Hz
- (Read only)
0x2DDD (PAR 100)
2
P103.00
Motor current %
x.x %
- (Read only)
0x6078 (PAR 103)
3
P106.00
Motor voltage
x VAC
- (Read only)
0x2D89 (PAR 106)
4
P150.00
Active error
-
- (Read only)
0x603F (PAR 150)
5
P200.00
Control source
Terminal mode [0]
Selection list
0x2824 (PAR 200)
6
P201.01
Frequency setp.
Analog input 1 [2]
Selection list
0x2860:001 (PAR 201/001)
7
P203.01
Start method
Normal [0]
Selection list
0x2838:001 (PAR 203/001)
8
P203.03
Stop method
Standard Ramp [1]
Selection list
0x2838:003 (PAR 203/003)
9
P208.01
AC input volt.
230 Veff [0]
Selection list
0x2540:001 (PAR 208/001)
10
P210.00
Min. frequency
0.0 Hz
0.0 ... 599.0 Hz
0x2915 (PAR 210)
11
P211.00
Max. frequency
50.0 Hz
0.0 ... 599.0 Hz
0x2916 (PAR 211)
12
P220.00
Acceleration time 1
5.0 s
0.0 ... 3600.0 s
0x2917 (PAR 220)
13
P221.00
Deceleration time 1
5.0 s
0.0 ... 3600.0 s
0x2918 (PAR 221)
14
P300.00
Motor ctrl mode
VFC open loop [6]
Selection list
0x2C00 (PAR 300)
15
P302.00
V/f curve
Linear [0]
Selection list
0x2B00 (PAR 302)
16
P303.01
Base voltage
230 V
0 ... 5000 V
0x2B01:001 (PAR 303/001)
17
P303.02
Base frequency
50 Hz
0 ... 599 Hz
0x2B01:002 (PAR 303/002)
Additional functions
Favorites
Accessing the "Favorites" with the keypad
162