Parameter
Name / value range / [default setting]
Info
Bit 31
0x2308
(PAR 516)
CANopen status
(CANopen status)
•
Read only
Display of the current CAN bus state.
0 Initialisation
CAN bus initialisation active.
•
The initialisation is started automatically at mains connection. During
this phase, the inverter us not involved in the data exchange process
on the CAN bus.
•
The standard values are re-written to all CAN-relevant parameters.
•
When the initialisation process has been completed, the inverter
automatically adopts the "Pre-Operational" state.
1 Reset node
"Reset Node" NMT command active.
•
Initialisation of all CAN-relevant parameters with the values stored.
2 Reset communication
"Reset Communication" NMT command active.
•
Initialisation of all CAN-relevant parameters with the values stored.
4 Stopped
Only network management telegrams can be received.
5 Operational
Parameter data and process data can be received.
127 Pre-Operational
Parameter data can be received, process data are ignored.
0x2309
(PAR 517)
CANopen controller status
(Controller status)
•
Read only
Status display of the internal CANopen controller.
1 Error active
The inverter is a fully-fledged communication node at the CANopen net-
work. It is able to transmit and receive data and to report faults.
2 Error passive
The inverter can only passively indicate faulty reception via the ACK
field.
3 Bus off
The inverter is electrically separated from the CANopen network. In
order to exit this state, the CANopen interface must be reset.
8.4.6
CANopen emergency telegram
If the error status changes when an internal device error occurs or is remedied, an emergency
telegram is sent to the NMT master once.
Details
•
The identifier for the emergency telegram is fixedly defined and is shown in
0x1014
.
•
In
0x1015
, a blocking time can be set, in order to limit the bus load in the case of emergency
telegrams following quickly in succession.
Parameter
Name / value range / [default setting]
Info
0x1014
COB-ID EMCY
•
Read only
Display of the identifier for emergency telegrams.
0x1015
Inhibit time EMCY
0.0 ... [0.0] ... 6553.5 ms
Blocking time which can be set in order to limit the bus load in the case
of emergency telegrams following quickly in succession.
8.4.7
CANopen heartbeat protocol
The heartbeat protocol can be used for node monitoring purposes within a CAN network.
Details
Basic procedure:
1
.
A heartbeat producer cyclically sends a heartbeat telegram to one or several receivers (con-
sumers).
2
.
The consumer(s) monitor(s) the heartbeat telegram for arrival on a regular basis.
The inverter can be configured as producer or as consumer to monitor up to four other nodes.
Parameter
Name / value range / [default setting]
Info
0x1016:000
(PAR 520/000)
Consumer heartbeat time: Highest subindex
(Cons heartbeat: Highest subindex)
•
Read only
Number of nodes to be monitored.
0x1016:001
(PAR 520/001)
Consumer heartbeat time: Node 1
(Cons heartbeat: Node 1)
0x00000000 ... [0x00000000] ... 0x00FFFFFF
Node ID and heartbeat time of node 1 which is to be monitored.
•
Format: 0x00nnhhhh (nn = node ID, hhhh = heartbeat time in [ms])
Configuring the network
CANopen
CANopen emergency telegram
115