11.14.2
Digital output 1
Settings for digital output 1.
Parameter
Name / value range / [default setting]
Info
0x2634:002
(PAR 420/002)
Function assignment of digital outputs: Digital output
1
(Digital outputs: DO1 function)
•
For possible settings see description for
0x2634:001 (PAR 420/001)
.
^
215
Assignment of a trigger to digital output 1.
Trigger = FALSE: X3/DO1 set to LOW level.
Trigger = TRUE: X3/DO1 set to HIGH level.
Notes:
•
An inversion set in
0x2635:002 (PAR 421/002)
is taken into considera-
tion here.
115 Release holding brake
TRUE if the holding brake is released (or should be released). Otherwise
FALSE.
0x2635:002
(PAR 421/002)
Inversion of digital outputs: Digital output 1
(DO inversion: DO1 inversion)
Inversion of digital output 1
0 Not inverted
1 Inverted
0x4016:003
Digital output 1: Cutout delay
0.000 ... [0.020] ... 65.535 s
Switch-off delay for digital output 1.
0x4016:004
Digital output 1: Switch-on delay
0.000 ... [0.020] ... 65.535 s
Switch-on delay for digital output 1.
0x4016:005
Digital output 1: Terminal state
•
Read only
Display of the logic state of output terminal X3/DO1.
0 FALSE
1 TRUE
0x4016:006
Digital output 1: Trigger signal state
•
Read only
Display of the logic state of the trigger signal for digital output 1 (without
taking a ON/OFF delay set and inversion into consideration).
0 FALSE
1 TRUE
11.14.3
NETWordOUT1 status word
Assignment of digital triggers to bit 0 ... bit 15 of the NETWordOUT1 status word.
Parameter
Name / value range / [default setting]
Info
0x2634:010
(PAR 420/010)
Function assignment of digital outputs:
NETWordOUT1 - bit 0
(Digital outputs: NETWordOUT1.00)
•
For possible settings see description for
0x2634:001 (PAR 420/001)
.
^
215
Assignment of a trigger to bit 0 of NETWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
51 Ready for operation
TRUE if operation is enabled AND no error is active. Otherwise FALSE.
0x2634:011
(PAR 420/011)
Function assignment of digital outputs:
NETWordOUT1 - bit 1
(Digital outputs: NETWordOUT1.01)
•
For possible settings see description for
0x2634:001 (PAR 420/001)
.
^
215
Assignment of a trigger to bit 1 of NETWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
69 Reversal active
TRUE if reversal is active. Otherwise FALSE.
•
Selection of the trigger for the "Reversal" function in
0x2631:013
(PAR 400/013)
.
0x2634:012
(PAR 420/012)
Function assignment of digital outputs:
NETWordOUT1 - bit 2
(Digital outputs: NETWordOUT1.02)
•
For possible settings see description for
0x2634:001 (PAR 420/001)
.
^
215
Assignment of a trigger to bit 2 of NETWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
50 Running
TRUE if motor is controlled (pulse width modulation on). Otherwise
FALSE.
0x2634:013
(PAR 420/013)
Function assignment of digital outputs:
NETWordOUT1 - bit 3
(Digital outputs: NETWordOUT1.03)
•
For possible settings see description for
0x2634:001 (PAR 420/001)
.
^
215
Assignment of a trigger to bit 3 of NETWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
56 Error active
TRUE if error is active. Otherwise FALSE.
Flexible I/O configuration
Configuration of digital outputs
Digital output 1
218
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: [email protected]