Parameter
Name / value range / [default setting]
Info
0x6074
Torque demand value
•
Read only: x.x %
Display of the interpolated setpoint torque.
•
100 % ≡ Motor rated torque
0x6076 (PAR 325)
0x6079
DC link circuit voltage
•
Read only: x.xxx V
Display of the current DC-bus voltage.
0x6085
(PAR 790)
Quick stop deceleration
(402quickst time)
0 ... [546000] ... 2147483647 pos. unit / s²
Change in velocity used for deceleration to a standstill if quick stop is
activated.
•
Setting only applies to CiA402 velocity mode.
•
For Lenze velocity mode, the deceleration time set in
0x291C
(PAR 225)
is effective.
0x6085 = ((initial speed of the motor [rpm]) / (duration of the ramp until
standstill [s])) * 1092
0x6502
(PAR 789)
Supported drive modes
(Supported modes)
•
Read only
Bit-coded display of the operating modes supported.
Bit 0 Not specified
Bit is not supported.
Bit 1 Velocity mode
Bit 2 Not specified
Bit is not supported.
Bit 3
Bit 4 Reserved
-
Bit 5 Not specified
Bit is not supported.
Bit 6
Bit 7 Cyclic synchronous position mode
Bit 8 Cyclic synchronous velocity mode
Bit 9 Cyclic synchronous torque mode
Bit 10 Reserved
-
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 16
Bit 17 Lenze speed mode
Bit 18 Reserved
-
Bit 19
Bit 20
Bit 21
Bit 22
Bit 23
Bit 24
Bit 25
Bit 26
Bit 27
Bit 28
Bit 29
Bit 30
Bit 31
0x6040
Controlword
0 ... [0] ... 65535
Mappable CiA402 control word with bit assignment in compliance with
CiA402 device profile.
Bit 0 Switch on
Bit 1 Enable voltage
Bit 2 Quick stop
Bit 3 Enable operation
Bit 4 Operation mode specific
Bit 5
Bit 6
Bit 7 Fault reset
Bit 8 n/a
Bit is not supported.
Additional functions
Device profile CiA402