85
5
Functional Description with Process Diagrams
5.2
Additional Burner Sequencer Functionality
5.2.1
Start Without Pre-Purge
NOTICE
The external signal for pre-purge suppression must be fail-safe.
5.2.1.1 Requirements
NOTICE
This function may only be activated if local regulations and the system configuration permit a
burner start without pre-purge or if sufficient pre-purge is ensured by other measures.
NOTICE
The function must be mapped.
5.2.1.2 Required Inputs/Outputs
The following digital inputs are required for the "pre-purge suppression" function:
•
Pre-purge suppression without testing for air pressure drop
If this input is mapped and activated, no pre-ventilation is carried out.
•
Pre-purge suppression for gas according to EN676
If this input is mapped and activated, no pre-purge according to EN676 is carried out in
gas operation.
For a description of the digital inputs, see chapter
3.2 Digital Input/Output Functions
5.2.1.3 Required Parameters
This function does not require any special parameters.
5.2.1.4 Functional Description
Pre-purge suppression by an external signal
The pre-purge function can be skipped with the ’Pre-purge suppression’ signal. If the signal is
present before ’Burner start-up’, the actuators move directly to the ignition position.
The external light monitoring of the flame scanner is carried out prior to the start of the flame
detection (P 803).
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...