System Description
3.2.2
Digital Outputs
List of digital outputs, version V1.0.3:
3.2.3
Assignment of Input/Output Functions
(logic signals to the input/output terminals)
The input and output functions (logic signals) of the physical terminals in the CMS are as-
signed using the I/O matrix in the CMS remote software. Among these, there are signals
whose use is mandatory and those whose use is optional. To help with this assignment, the
CMS remote software provides a link matrix and a link table.
See chapter
7.3.3.4, section
Pressure before valves > min.
Signal to switch off if pressure < min.
If the pressure drops below the minimum value, a
fault shut-down is initiated.
4 Signals for the chains 1 ... 4 are possible.
Safety chain input
User-configurable input for a safety chain function,
see chapter
Curve set selection
Signal for curve set pre-selection (max. 16 possible),
see chapter
Firing rate+/firing rate
−
These signals increase or reduce the burner firing
rate if the regular firing rate input is configured to TPS.
Soft PLC input signal
User-programmable input via PLC
* The signals "Main flame present" are logically connected in series (AND operation).
Input
Description
Output
Description
Pilot valve 1+2
Activates the pilot valves
Fuel train 1–4
valves 1+2
Activates valve 1 and valve 2 in fuel
trains 1–4
Spark igniter per fuel train
1–4
Activates the spark igniter for fuel trains 1–4
Purge valve 1–4
Activates purge valves 1–4
Fault status signal
Indicates that CMS is in fault state.
Fan
Activates the fan
Fuel pump
Activates the fuel pump
Atomiser steam 1–4
Activates atomiser steam valves 1–4
Pilot fan 1–4
Activates the motor for pilot fans 1–4
Activation of the mechanic
ratio control
Provides floating contacts for controlling a servo
motor in combination with a mechanic ratio control.
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...