217
8
CO/O
2
Control
NOTICE
See safety concept in chapter
6. Set response threshold of the CO detection on the LT3-F.
8.10.7 Set and Optimise the CO Response Threshold on LT3-F
7. Put CO control into operation.
8.10.8.1 Commissioning with UI400
.
8.10.8.2 Operating with PC Remote Software
.
8. Set control parameters and dead time of the O
2
trim on CMS.
Setting the 'Proportional Factor' and 'Dead Time' Control Parameters
Setting the 'Proportional Factor' and 'Dead Time' Control Parameters
9. Check settings on CMS and LT.
Exiting SETTING Mode
– via CMS Remote Software
10. Back up dataset from CMS and LT3-F using CMS Remote Software (download).
Information on this is included in the basic documentation (publication no. DLT3140)
The commissioning of CO/O
2
control is now complete.
8.10.2 Putting the Electronic Ratio Control System into Operation
Commissioning of the electronic ratio control system and O
2
measurement, as described in
the device-specific instructions referred to in Chapter
1.1 Validity of these Instructions
.
The integrated CO/O
2
control remains deactivated.
7 Operating Control and Displays
P 200 = 0
CO control is deactivated.
P 200 = 1
Standard (O
2
= OIL/CO = Gas)
(see chapter
8.10.8.2 Operating with PC Remote Software
WARNING!
An incorrect setting can result in explosion.
This can result in severe injuries or death.
Note the burner manufacturer's instructions with regard to settings.
The burner (basic setting without O
2
trim or CO control) must be set so that it burns stably
under all operating conditions and the emission limit values are observed. For the ’Deactivated
CO/O
2
control’ operating condition, a correct offset for inactive control with excess air must be
set (at the factory).
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...