Safety
2.3.2
Installation Notes
•
Always lay the high-voltage ignition conductor separately and as far away as possible from
the device and the other conductors.
•
Observe the relevant local and national regulations when wiring the electrical cables within
the burner.
•
Tighten the screw terminals using a tightening torque >0.5Nm.
•
Supply the feed cable with L, N and PE only. The N neutral conductor must not have po-
tential difference to the PE protective conductor.
•
The pre-fuse on CMS is permitted to be max. 8
A fast-acting per output module (MCC and
output module).
•
Ensure that strain relief of the connected conductors complies with relevant standards
(e.g. DIN EN 60730 and DIN EN 60 335).
•
Ensure that no spliced strands can come into contact with any of the adjacent connec-
tions. Use suitable end splices.
•
To replace or disconnect the plug-in connectors, all poles of the plant must be disconnect-
ed from the mains.
•
The connection between the actuating drives and actuator devices for the fuel and com-
bustion air, as well as to any additional actuator devices that may be in use, must be pos-
itive locking.
•
When wiring components with protective extra low voltage (SELV), and in connected de-
vices, make sure there is a safe separation to the mains voltage.
•
Only connect passive or non-interacting devices to the CMS firing rate outputs (e.g. relay
without additional power supply). In the event of a fault, a supply of 230 V must be exclud-
ed to the CMS via these terminals.
•
Use gold-plated silver contacts on 24 VDC inputs.
•
To avoid faults on the LSB, the termination via P 1010 must be switched to active on the
first and last device connected to the bus.
•
Via installation of the CMS modules, the flame sensor and all additional equipment, the
minimum protection class IP40 – or IP54 for use outdoors – must be ensured in accord-
ance with EN 60529.
•
The analogue inputs connected to the modules must have the same potential as the pow-
er supply of the CMS system.
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...