105
5
Functional Description with Process Diagrams
5.4.3.4 Controlled by Atmospheric Conditions
5.4.3.5 Limiting the Firing Rate Controller
P no.
Description
Attributes
48
Controller setpoint 1 (for constant control/min. value for control by atmospheric condition)
Controller setpoint 1 minimum. Setting the minimum set point for the controller controlled by
atmospheric conditions in °C or bar.
The setting is active if the input ’Setpoint changeover’ = 0.
If the firing rate controller is configured as a constant controller, setpoint 1 is set here
Write: 0/GUI/UI
Read: 0
Default:84
Min: -32768
Max: 32767
49
Controller 1 maximum value (only for control by atmospheric conditions)
V1.0.0.0
Controller setpoint 1 max. for control by atmospheric conditions
Enter the setpoint maximum for the controller in °C or bar. The setting is active if the input
’Setpoint changeover’ = 0.
Write 0/GUI/UI
Read: 0
Default: 84
Min: -32768
Max: 32767
50
Controller 2 setpoint (constant control/min. value for control by atmospheric conditions)
V1.0.0.0
Enter the setpoint minimum for the controller controlled by atmospheric conditions in °C or
bar. The setting is active when the input ’Setpoint changeover’ = 1.
If the firing rate controller is configured as a constant controller, setpoint 2 is set here.
Write: 0/GUI/UI
Read: 0
Default: 84
Min: -32768
Max: 32767
51
Controller 2 maximum value (only for control by atmospheric conditions)
V1.0.0.0
Controller setpoint 2 maximum for control by atmospheric conditions
Enter the setpoint maximum for the controller in °C or bar. The setting is active if the input
’Setpoint changeover’ = 1.
Write: 0/GUI/UI
Read: 0
Default: 84
Min: -32768
Max: 32767
52
Temperature range minimum
53
Temperature range maximum
V1.0.0.0
Upward limitation of the set point for control by atmospheric conditions 0,1 °C or Digit.
This is the lower limit of the outdoor temperature.
0 ... 249 = 0,0 ... 24,9 °C
250 ... 500 = -25,0 ... 0,0 °C
Upward limitation of the set point for setpoint shift in 0,1 mA or Digit. This is the lower limit of
the current input (min. = 0 max. = 500).
0 = 0,0 mA
40 = 4,0 mA
200 = 20,0 mA
Write: 0/GUI/UI
Read: 0
Default: 25
Min: -32768
Max: 32767
P no.
Description
Attributes
43
Start-up sequence: max. actual value
V1.0.0.0
Parameter for start-up sequence:
max. start-up temperature/pressure related to actual value input.
Set the temperature to which the start-up sequence shall be active until reaching.
Write: 0/GUI/UI
Read: 0
Default: 0
Min: 0
Max:999
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...