252
9
Faults
9
Faults
The fault status signal is also written to a separate document (publication no. DLT7201).
Restarts
For some faults automatic restarts can be configured in the CMS. In this context, it is important
to ensure that the set restarts comply with the normative and safety-related requirements of
the system.
No.
Description
D1
D2
Extra
001 - 019 Internal fault
0
0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
020 - 067 Internal fault
0
0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
068
IO: Motor overload shutdown has been triggered
Overload shutdown of a TPS motor output or the VS
relay output has been triggered.
Affected motor(s),
bit coded:
AEC-TPS:
Bit0: TPS motor 1
Bit1: TPS motor 2
0
R = 0
Power ON Reset
069 - 096 Internal fault
0
0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
097
Short circuit in potentiometer 1
Plausibility test of potentiometer 1 during operation:
Short circuit between potentiometer reference and
ground.
Potentiometer no.
0
R = 0
Reset
098
Failure in potentiometer 1: Reference voltage or ref-
erence current
Plausibility test of potentiometer 1 during operation:
Fault in reference voltage or potentiometer current
Reference voltage
Potentiometer
current
R = 0
Reset
099
Failure in potentiometer 2 reference current or refer-
ence voltage
Plausibility test of potentiometer 2 during operation:
Fault in reference voltage or potentiometer current
Reference voltage
Potentiometer
current
R = 0
Reset
100
Invalid potentiometer configuration
The potentiometer plausibility check at Power ON
detected an invalid configuration.
Problem:
– Reference voltage is missing
– Current in potentiometer without reference voltage
– Variant with redundancy but only one
potentiometer is connected
Bit mask of poten-
tiometer current:
Potentiometer 1
Bit 0 = 1
Bit 1 = 2
Potentiometer 2
Bit 2 = 1b
Bit 3 = 2b
Bit mask of
reference voltage
Potentiometer 1
Bit 0 = 1
Bit 1 = 2
Potentiometer 2
Bit 2 = 1b
Bit 3 = 2b
R = 0
Power ON Reset
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...