248
8
CO/O
2
Control
0052
CO fault
ot
The CO edge signal is not plausible.
The CO edge signal was present constantly for more than 60 s.
The controller cannot control out of the CO.
– Check/adjust the triggering threshold for the CO edge on the
LT.
– Check/adjust correction range (P703).
– Check/adjust electronic ratio curves.
– Check/replace probe for correct function.
– Check/replace LT
0053
CO fault
ot
The CO edge signal is not plausible.
Permanent CO controller switch-off.
CO edge signal persisted for more than 300 s.
– Reset fault by a manual acknowledgement of the fault
or with a burner restart
– Check/adjust correction range (P703).
– Check/adjust electronic ratio curves.
– Check/replace probe for correct function.
– Check/replace LT
0054
CO fault
ot
The CO edge has been exceeded for too long after ignition.
The CO edge has been exceeded permanently for more than 120 s. The
controller cannot control out of the CO.
– Check/adjust the triggering threshold for the CO edge on the
LT.
– Check/adjust correction range (P703).
– Check/adjust electronic ratio curves (ignition point).
– Check/replace probe for correct function.
– Check/replace LT
0055
CO fault
od
The CO edge has been exceeded for too long after ignition.
The CO edge has been exceeded permanently for more than 240 s.
The controller cannot control out of the CO.
The CO detection can be switched off after ignition by P234
(P 234
0)
– Check/adjust the triggering threshold for the CO edge on the
LT.
– Check/adjust correction range (P703).
– Check/adjust electronic ratio curves (ignition point).
– Check/replace probe for correct function.
– Check/replace LT
No.
Fault/
information
Comment
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...