Faults
No.
Description
D1
D2
Extra
355
Ignition in mixed operation
FAT tries to ignite in a mixing curve
Internal
information
Fuel train
R = 0
Reset
356
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
information
0
R = 0
Power ON Reset
357
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
information
0
R = 0
Power ON Reset
380
Band failure: Setpoint is outside the expected range
The watchdog processor detects a band failure.
Setpoint or actual value of an actuator is not in the
expected range.
Setpoint minimum
lower 12 bits: set-
point maximum
Channel number
in the bits above
bit 12
R = 0, 0, 0, 0
Reset
381
Actuator dynamics is missing
The ÜP has not detected the required dynamics for
at least one actuator.
Problem:
The actual position of the actuator has not
changed in the last 24 hours.
– Check air damper and gas damper for jamming.
– In case of stiffness, clean the damper and
make it smooth running again.
– Check the function of the actuator without
damper and replace if necessary.
– Reset fault and switch mains voltage OFF
and ON again.
– If the error still exists, replace the device.
0: Actuator
dynamics
1: Correction
channel dynamics
Number of actua-
tor or correction
channel (starting
with 0)
R = 0
Reset
382
Monitoring data from the bus are missing
The watchdog processor requires certain data for
monitoring. These are read at the bus. Currently
required data are missing
Reason:
– Invalid channel configuration
– A non-existing channel is activated
– An inactive channel is marked in the channel
enable mask
1: Actual curve
set
3: Actual value,
channel no. in
P 2
4: Setpoint value,
Channel no. in
P 2
5: Firing rate
value
P 1 = 3 or 4,
Channel no.
(starting at 0)
P 1 = 5,
special fault code
R = 0
Power ON Reset
383
Invalid curve set selection
– Ensure that there is no fuel change during curve
set programming.
– Reset fault
0
0
R = 0
Power ON Reset
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...