Functional Description with Process Diagrams
5.4
Burner Firing Rate Controller
5.4.1
Requirements
NOTICE
Purchase option: This function must be purchased and mapped.
5.4.2
Required Inputs/Outputs
The actual value is assigned to the analogue input in the IO-Matrix dialogue of the CMS Re-
mote Software.
The setpoint values can be switched by means of the digital input signal ’PLC firing rate con-
troller input setpoint changeover’.
•
Input HIGH: setpoint 1
•
Input LOW: setpoint 2
5.4.3
Required Parameters
5.4.3.1 Configuration
Activate or deactivate the firing rate in P0040.
Set the PID settings in P0057, P0058 and P0059.
P no.
Description
Attributes
40
Operating mode of the firing-rate controller (0-OFF; 1-constant control; 2-controlled by
atmospheric conditions)
V1.0.0.0
Operating mode of the firing-rate controller
0 = OFF
1 = constant control
2 = controlled by atmospheric conditions
Write: 1/GUI/UI
Read: 0
Default: 0
Min: 0
Max: 2
57
P Term
V1.0.0.0
Proportional term of the controller.
Write: 0/GUI/UI
Read: 0
Default: 3
Min: 0
Max: 65535
58
I Term
V1.0.0.0
Integral term of the controller
Write: 0/GUI/UI
Read: 0
Default: 60
Min: 0
Max:999
59
D Term
V1.0.0.0
Derivative term of the controller
Write: 0/GUI/UI
Read: 0
Default: 10
Min: 0
Max: 65535
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...