Safety
formed at the shut-off limit of the CO/O
2
Start-up O2 Monitoring Shut-off Limits
•
Testing at the shut-down thresholds is also not required if the parameter setting for the
tolerance at the air deficiency side is 0 digits. Proof must be obtained of the correct setting
of this parameter during commissioning.
•
In cases where mixed combustion is activated (simultaneous combustion of more than
one fuel), the precomputed setpoint curves must be verified during commissioning by
checking the combustion characteristics.
The operating modes must be analysed in terms of excess air and the combustion char-
acteristics must be measured during the operating mode in which the lowest excess air
value has been configured.
Safe and stable combustion must be ensured during the activation and deactivation of a
fuel feed.
2.3.7
Components/Devices of External Manufacturers
Requirements for third-party manufacturers whose devices are connected to the com-
munication interface of the CMS.
All bus nodes connected directly to the CMS (Ethernet devices, e.g. switches) must guarantee
insulation in accordance with DIN EN 60950-1
All devices connected to SELV terminals (sensors, converters, frequency inverters) must
guarantee/maintain insulation in accordance with DIN EN 60730-1 SELV.
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...