
249
8
CO/O
2
Control
8.11.4
O
2
Trim Faults
NOTICE
Depending on the parameter settings, either O
2
trim is deactivated or a fault switching of the
burner is triggered (P 142).
Factory setting: P 142 = 0 (CO/O
2
control is inactive, burner is not switched off)
O
2
fault example:
Fig. 8-40 Display of an O
2
monitoring fault
O
2
measured value at pre-purge is too large
24%
No.
CO faults -
information
Fault description
0001
O
2
fault
od
O
2
measured value during pre-purge is too low (P104).
O
2
actual value at pre-purge too low.
Setpoint: > 16.0% O
2
– Check the probe.
– Perform an offset calibration
0002
O
2
fault
od
O
2
measured value during pre-purge is too high (P103).
O
2
actual value at pre-purge too high
Setpoint: <24.5 vol. % O
2
Probe is too cold or the offset calibration is not performed.
– Check the probe’s internal resistor.
– Perform an offset calibration.
0003
O
2
fault
od
O
2
measured value after ignition is too high (P105).
The probe dynamics cannot be detected.
Setpoint: <14.0 vol. % O
2
(factory setting)
The fault occurs after a timeout if no O
2
value is transmitted by
LSB.
– Check if Lambda Transmitter is in adjustment mode.
If yes: Finish adjustment mode.
– No value is indicated:
Check LSB.
– Is the probe hot enough?
0004
O
2
fault
ot
od
No probe dynamics - O
2
trim is deactivated (P118)
No probe dynamics can be detected.
–Correction range in CMS too small or set to ’0’
0 = Default setting. The value must be set by the customer
for each specific system.
– Set the correction range.
– Is the servomotor at the upper range limit?
Reprogram the electronic ratio control.
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...