211
8
CO/O
2
Control
8.6.3
Optimisation Strategy
The optimisation strategy includes searching for the optimum working point of the furnace
near the emission edge, adjusting this accordingly, maintaining it, optimising further, if neces-
sary, and monitoring.
To do this, the fuel-air mixture is dynamically modified without influencing the power control
unit in the direction of a lower lambda value (less air, more fuel). The beginning of incomplete
combustion is shown by a strong signal increase and signal dynamics.
From this point on, the air-fuel mixture is slightly modified again in the direction of a greater
lambda value (more air/less fuel). The optimum working point is found.
The working points determined in this way are subjected to a plausibility analysis. Working
points outside of this are discarded and recalculated. This procedure is repeated cyclically so
that the optimum working points are always maintained even in changing weather and system-
related conditions.
If the KS1D Combination probe detects unburned residue (CO/H
2
), for example as a result of
changed, system-specific conditions, the working point is immediately shifted in the direction
of a greater lambda value (more air, less fuel).
The simultaneously measured O
2
value is not required for CO control itself. It is only required
for monitoring and visualisation purposes. If it is not possible for combustion-related reasons
to run to the CO edge over the entire firing range, there is the option of switching smoothly
from CO control to O
2
trim depending on the firing range. With multi-fuel burners, you can se-
lect whether CO control or the O
2
trim is active depending on the fuel.
8.6.4
Advantages of CO Control over O
2
Trim
•
Higher energy savings through continuous self-optimisation in every firing-rate point
•
Better control performance through significantly shorter setting times
•
Excess air independent
•
Failsafe
•
Higher operating safety
•
Robust
•
Low-maintenance
8.7
Operating Control and Displays
8.7.1
Is CO Control or O2 Trim Activated?
Factory settings
Oil
O
2
trim
Gas
CO control
P 100
AL 1
=
1
O
2
standard trim with optimisation curve
P 101
AL 0
=
0
1
O
2
trim OFF
O
2
trim ON
P 200
AL 1
=
1
CO controller type: Gas = CO control, oil = O
2
trim
P 203
AL 0
=
0
1
CO controller OFF
CO controller ON
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...