CO/O
2
Control
Fig. 8-1 Correction range of the CO controller
The upper limit of the correction range ensures that all errors leading to a movement of the
controller in the direction of excess air only move the actuating devices up to an upper limit
that is still safe.
If this upper limit is exceeded in spite of this, and the correction range is violated, the controller
recognises this problem.
In contrast, errors that lead to the CO controller regulating in the direction of a lack of air must
be detected beforehand.
To handle this error, two additional monitors are implemented, which detect in a variety of
ways by means of the O
2
and CO sensor when the exhaust gas falls below a critical O
2
min-
imum value or exceeds a CO
e
value (O
2
minimum monitor /U-CO
e
maximum monitor).
A "CO
e
dynamics test" and "O
2
dynamics test" ensure that these monitors are working cor-
rectly. These tests check whether the probes still react to changes of the fuel-air mixture by
means of a short modification of the exhaust gas composition.
Monitors for limit values have a timeout of < 20 s (<0.4 % O
2
). This is due to the long running
time of the exhaust gas flow from the burner to the exhaust gas sensor system and the thus
very slow control function.
8.3
Requirements
To use CO/O
2
control, one of the following systems must be implemented:
•
LT3-F in combination with KS1D
•
LT1/LT2 for O
2
measurement in combination with LT2 and KS1D
8.4
Required Inputs/Outputs
•
Corrections to the electronic ratio control
•
Sensor input to LT3
8.5
Required Parameters
All parameter groups for CO controller and CO monitoring are required for CO/O
2
control.
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...