CP - Parameter
Operation
4
3
KEB COMBIVERT F5-M / S
10
Name: Basis
17.05.04
Chapter
Section
Page
Date
©
KEB Antriebstechnik, 2003
All Rights reserved
F5-MULTI:
Rated motor power
Adjustment of the rated motor power according to the name plate. The factory setting
depends on the unit size (see 4.3.7 ÑFactory Settingsì).
Adjustment range:
0,35...400,00 kW
Resolution:
0,01 kW
Factory setting:
LTK
F5-MULTI:
Motor cos (phi)
Adjustment of the motor cos(phi) according to the name plate. The factory setting
depends on the unit size (see 4.3.7 ÑFactory Settingsì).
Adjustment range:
0,50...1,00
Resolution:
0,01
Factory setting:
LTK
F5-MULTI:
Rated motor voltage
Adjustment of the rated motor voltage according to the name plate and the connection
(Y /
∆
). The factory setting depends on the unit size (see 4.3.7 ÑFactory Settingsì).
Adjustment range:
120...500 V
Resolution:
1 V
Factory setting:
LTK
F5-SERVO:
Rated motor current
Adjustment of the rated motor current according to the name plate. The factory setting
depends on the motor.
Adjustment range:
0,0...710,0 A
Resolution:
0,1 A
Factory setting:
LTK
F5-SERVO:
Motor voltage constant
Adjustment range:
0...1000
Resolution:
1
Factory setting:
LTK
Adjustment of the motor voltage constant according to the data sheet. The motor
voltage constant is the peak value of the voltage between the phases at a speed of
1000 rpm (unit: V / 1000 rpm). The factory setting depends on the motor.
F5-SERVO:
Motor winding inductance
Adjustment range:
0,01...500,00 mH
Resolution:
0,01 mH
Factory setting:
LTK
Adjustment of the motor winding inductance according to the data sheet. The factory
setting depends on the motor.