6
Functional Description
Analog In- and Outputs
6
2
9
KEB COMBIVERT F5
Name: Basis
Chapter Section
Page
Date
©
KEB Antriebstechnik, 2002
All rights reserved
04.05.04
6.2.9
Selection Set
Point-/Auxiliary
Input (An.30)
Following functions are combined in An.30:
- Bit 0..2
Selection of the analog input (AN1, AN2, AN3) as REF analog
- Bit 3..5
Mode of the AUX-Function
- Bit 6..10
Selection source 1 for the AUX-Function
- Bit 11..15 Selection source 2 for the AUX-Function
For possible expansions not all values are defined in the bit groups. Not defined values
have the same function as value 0. The sum of the respective values is to be entered.
Assignment of the analog inputs:
Bit 0..2
Function
Value
REF analog
0
AN1 (ru.28) (default)
1
AN2 (ru.30)
x
2
AN3 (ru.32)
x
Bit 3..5
Function
Value
Mode of the AUX-Function
0
Source 1 (default)
8
Source 1 + Source 2
16
Source 1 * (100% + Source 2)
24
Source1 * Source 2
32
Source1 absolute
Bit 6..10
Function
Value
Aux-input source 1
0
AN1 (ru.28)
64
AN2 (ru.30) (default)
x
128
Percental setpoint value (op.5)
192
Motorpoti (ru.37)
256
Process controller output (ru.52)
320
AN3 (ru.32)
x
Bit 11..15
Function
Value
Aux-input source 2
0
AN1 (ru.28)
2048
AN2 (ru.30) (default)
x
4096
Percental setpoint value (op.5)
6144
Motorpoti (ru.37)
8192
Process controller output (ru.52)
11240
AN3 (ru.32)
x
x: not for control card BASIC