Functional Description
Protective Functions
6.7.10 Special
Functions
Here functions are summarised which affect the behaviour of the inverter in certain
operating cases.
Special Functions (Pn.65)
Bit Value
Meaning
0
Switching behaviour GTR7 (see Chapter 6.7.9 „GTR-control“)
0
GTR7 does not switch in the status „LS“ (default)
1
GTR7 switches dependent on the level also at „LS“
1
This bit determines the error-/warning message, that is triggered at the
switching of an external error input (Pn.4).
0
Pn.4 is selection for external error-/warning message. The response to
this message (A.EF/E.EF) is defined with Pn.3.
1
Pn.4 is selection for error undervoltage (E.UP). Pn.3 has no function in
this case.
2
Status, if the power circuit is not ready (no_PU). This setting applies to
the output switching conditions do.0...7 = 4...6 and the ERROR-bit in
the status word (sy.44/sy.51 Bit 1).
0
State „no_PU“ is an Error
1
State „no_PU“ is an Error
3
Wie bei LS kann der GTR7 auch bei Fehler aktiviert levelabhängig wer-
den.
Ausnahme: Bei Öffnen der Reglerfreigabe und bei nicht ver-
sorgtem Leistungsteil (no_PU) wird der GTR7 abgeschaltet.
0
GTR7 nicht aktiv bei Fehler
1
GTR7 levelabhängig bei Fehler
(not at F5-B)