Functional Description
Analog In- and Outputs
2
10
6
Name: Basis
KEB COMBIVERT F5
Chapter
Section
Page
Date
04.05.04
©
KEB Antriebstechnik, 2002
All rights reserved
6.2.10 Brief Description
Analog Outputs
The KEB COMBIVERT has three programmable analog outputs (ANOUT1...4). Para-
meters An.31 and An.36 allow the selection of one size each which is given out at the
outputs X2A.5 / 6. The third and fourth analog output (An.41/47) is not led to the
terminal strip, it can be output as switching condition 42, e.g. 43 with the digital outputs
as PMW-signal. By means of the characteristic amplifier (An.33...35 / 38...40 / 43...45/
49...51) the analog signals can be adapted to the requirements. The ru-parameters
show the current size before and after the amplification. The period time for the PWM-
signal can be adjusted with An.46/52.
Fig. 6.2.10
Principle of analog output
An.31
An.33
An.34
An.35
X2A.5
ANOUT1
X2A.8
AGND
0...±100%
0...±10V
ru.34
ru.33
An.36
An.38
An.39
An.40
X2A.6
ANOUT2
X2A.9
AGND
0...±100%
0...±10V
ru.36
ru.35
An.41
An.43
An.44
An.45
PWM
100%
An.46
An.47
An.49
An.50
An.51
PWM
100%
An.52
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
ru.7
ru.1
±ru.7
±ru.1
ru.20
ru.18
ru.15
ru.17
An.xx
±ru.52
ru.52
ru.17
ru.38
ru.46
±ru.12
ru.12
±ru.11
ru.11
-
±ru.2
ru.2
Observe the
different functional range of the
hard- and software of the different control
cards !
The reference values of real and set values
depends on ud.2.
100% correspond to An.31/36/41/47 =
absolute actual value (100 Hz/1000 min
-1
)
absolute set value (100 Hz/±1000 min
-1
)
actual value (±100 Hz/±1000 min
-1
)
set value (±100 Hz/±1000 min
-1
)
output voltage (500 V)
DC voltage (1000 V)
apparent current (2 * I
rated
)
active current (2 * ±I
rated
)
digital An.32/37/42/48
external PID output (±100 %)
absolute ext. PID output (100 %)
absolute active current (2 è I
rated
)
Power mod. temperature (100
∞
C)
Motor temperature (100
∞
C)
actual torque (F5-M/S)
absolute actual torque (F5-M/S)
set torque (F5-M/S)
absolute set torque (F5-M/S)
system deviation/speed controller (±100Hz/±1000min
-1
)
speed reference variable (±100 Hz/±1000 min
-1
)
absolute speed reference variable (100 Hz
/
1000 min
-1
)
do.0...do.7
value Ñ42ì
do.0...do.7
value Ñ43ì