KEB COMBIVERT F5
12
Name: Basis
04.05.04
©
KEB Antriebstechnik, 2002
All Rights reserved
Product Description
Summary
Chapter
Section
Page
Date
Inverter Size
28
29
30
31
Housing Size
W
Phases
3
2 x 3
3
2 x 3 2 x 3 2 x 3
Output nominal power
[kVA]
256
319
395
436
Max. rated motor power
8)
[kW]
200
250
315
355
Output nominal current
[A]
370
460
570
630
Max. short time current
1)
[A]
463
575
713
787
OC-tripping current
[A]
555
690
855
945
Nominal input current
[A] 410 2x205 510 2x255 2x315 2x350
Max. permissible mains fuse (inert)
[A] 550 315
700
400
450
550
Rated operating frequency
[kHz]
2
2
2
2
Max. operating frequency
[kHz]
4
2
2
2
Power loss at nominal operating
[W]
3500
4200
5100 5600
Stall current at 4kHz
3)
[A]
370
ñ
ñ
Max. heat sink temperature TOH
[
∞
C]
90
90
90
60
Motor line cross section
4)
[mm
≤
]
2x95
2x150
2x185 2x185
Min. braking resistor
5)
[Ohm]
1,2
1,2
1,2
1,2
Typ. braking resistor
5)
[Ohm]
2,2
1,7
1,3
ñ
Max. braking current
[A]
660
660
660
660
Overload curve
2
Tightening torque for terminals
[Nm]
25...30
Mains voltage
6)
[V]
305...500 ±0
Mains frequency
[Hz]
50 / 60 +/- 2
Output voltage
[V]
3 x 0...U mains
Output frequency
[Hz]
see control card
Max. shielded motor line length
[m]
50
Storage temperature
[
∞
C]
-25...70
∞
C
Operating temperature
[
∞
C]
-10...45
∞
C
-10...45
∞
C
7)
Model / protective system
IP20
Relative humidity
max. 95% without condensation
EMC tested in accordance with ...
EN 61800-3
Climatic category
3K3 according EN 50178
1) With the regulated systems F5-M as well as F5-S 5% are to be subtracted as control reserve.
2) Fuses of type Ferraz Shawmut 6,6 UD Type 31
3) Max. current before the responding of the OL2-function (only F5-M; F5-S; F5-A)
4) Recommended minimum cross section for rated power and a cable length of upto 100m (copper)
5) This data is only valid for units with internal brake transistor (see "unit identification")
6) Rated voltage 400V; at mains voltage
≥
460V multiply the rated current with factor 0.86.
7) The temperature range is only valid for the control circuit. For the power circuit the temperature range is depending on
the control cabinet installation and the cooling system.
8) 31.F5 only watercooled.