The User Manual of JAC200 Series General Frequency Converter
- 93 -
The ones place, tens place, and hundreds place of the function code correspond to analog inputs AI and
Key
potentiometer
.
If 0 is selected, the setting that the analog corresponds to is the “minimum input corresponding setting”
(F4-14, F4-24) of the curve defined by the function code, when AI input is less than the “minimum input”.
If 1 is selected, the setting that the analog corresponds to is 0.0%, when AI input is less than the minimum
input.
F4-35
DI1 delay time
Default value
0.0s
Set range
0.0s
~
3600.0s
F4-36
DI2 delay time
Default value
0.0s
Set range
0.0s
~
3600.0s
F4-37
DI3 delay time
Default value
0.0s
Set range
0.0s
~
3600.0s
It is used for setting the delay time that the frequency converter controls to respond to the state change of
terminal DI.
Currently, only DI1, DI2 and DI3 possess the function of setting delay time.
F4-38
Valid mode selection 1 of
terminal DI
Default value
00000
Setting
Ones place
Valid state setting of terminal DI1
0
Active-high level
1
Active-low level
Tens place
Valid state setting of terminal DI2 (0 ~1, the same as
above)
Hundreds
place
Valid state setting of terminal DI3 (0 ~1, the same as
above)
Thousands
place
Valid state setting of terminal DI4 (0 ~1, the same as
above)
Myriabit
Reserved
It is used for setting the valid state mode of the digital value input terminal.
When active-high level is selected, the corresponding terminal DI is valid when connected with COM. But
it’s invalid when disconnected.
Group F5 Output terminal
The standard configuration of the JAC200 series frequency converter includes one multifunctional analog
output terminal, one multifunctional digital value output terminal, one multifunctional relay output terminal.
F5-02
Relay output function selection (T/A-T/C)
Default value
2
F5-04
DO output function selection (output terminal of open
collector)
Default value
1