The User Manual of JAC200 Series General Frequency Converter
- 127 -
Fig. 6-26 The diagram of process PID principles
FA-00
PID given source
Default value
0
Set range
0
FA-01 setting
1
AI
2
Reserved
3
Key
potentiometer
4
Reserved
5
Communication
6
Multi-stage instruction
FA-01
PID given value
Default value
50.0%
Set range
0.0%
~
100.0%
This parameter is used to select the target value of given channel of PID process
The set target value of PID process means relative value, the set range is 0.0%~100.0%. Meanwhile the
feedback value of PID is also relative value, and making the two relative values the same is the function of
PID.
FA-02
.
Default value
0
Set range
0
AI
1
Reserved
2
Key
potentiometer
3
Reserved
4
Reserved
5
Communication
6
Reserved
7
Reserved
8
Reserved
This parameter is used to select feedback signal channel of PID process.
The feedback value of process PID is also the relative value, the set range is 0.0%~100.0%.
FA-03
PID function direction
Default value
0