The User Manual of JAC200 Series General Frequency Converter
- 23 -
Function
code
Name
Set range
Default
value
Chan
ge
motor
dependent
F1-05
Rated speed of motor
1rpm
~
65535rpm
Model
dependent
★
F1-06
Stator resistance of
asynchronous motor
0.001Ω ~ 65.535Ω (Power of frequency
converter<=55kW)
0.0001Ω ~ 6.5535Ω (Power of frequency
converter>55kW)
Tuning
parameter
★
F1-07
Rotor resistance of
asynchronous motor
0.001Ω ~ 65.535Ω (Power of frequency
converter<=55kW)
0.0001Ω ~ 6.5535Ω (Power of frequency
converter>55kW)
Tuning
parameter
★
F1-08
Leakage inductive
reactance of
asynchronous motor
0.01mH~655.35mH (Power of frequency
converter<=55kW)
0.001mH~65.535mH (Power of frequency
converter >55kW)
Tuning
parameter
★
F1-09
Interaction inductive
reaction of
asynchronous motor
0.1mH~6553.5mH (Power of frequency
converter<=55kW)
0.01mH ~ 655.35mH (Power of frequency
converter>55kW)
Tuning
parameter
★
F1-10
No-load current of
asynchronous motor
0.01A ~ F1-03 (Power of frequency
converter<=55kW)
0.1A ~ F1-03 (Power of frequency
converter>55kW)
Tuning
parameter
★
F1-37
Tuning selection
0: No operation
1: Static tuning of asynchronous motor
2: Complete tuning of asynchronous motor
3: Static complete parameter identification
0
★
Group F2 Vector control parameter of the first motor
F2-00
Proportional gain 1
of speed loop
1
~
100
30
☆
F2-01
Integral time 1 of
speed loop
0.01s
~
10.00s
0.50s
☆
F2-02
Switching Frequency
1
0.00
~
F2-05
5.00Hz
☆
F2-03
Proportional gain 2
of speed loop
1
~
100
20
☆
F2-04
Integral time 2 of
speed loop
0.01s
~
10.00s
1.00s
☆