The User Manual of JAC200 Series General Frequency Converter
- 122 -
second time failure
F9-34
The operation time in the
second time failure
F9-37
The frequency in the first time
failure
The same as F9-17~ F9-24
F9-38
The current in the first time
failure
F9-39
The bus voltage in the first
time failure
F9-40
The input terminal state in the
first time failure
F9-41
The output terminal in the first
time failure
F9-42
The frequency converter state
in the first time failure
F9-43
The power-on time in the first
time failure
F9-44
The operation time in the first
failure
F9-47
Select 1 for the failure protection
action
Default value
00000
Set range
Ones place
Motor overload (Err11)
0
Free stop
1
Stop according to stop method
2
Continue operation
Tens place
Input default phase (Err12) (The same as ones place)
Hundreds
place
Output default phase (Err13) (The same as ones place)
Thousands
place
External failure (Err15) (The same as ones place)
Myriabit
Communication abnormity (Err16) (The same as ones
place)
F9-48
Select 2 for the failure protection
action
Default value
00000
Set range
Ones place
Encoder failure (Err20)
0
Free stop
1
Switch into VF, stop according to stop mode
2
Switch into VF, continue operation