The User Manual of JAC200 Series General Frequency Converter
- 40 -
Function
code
Name
Set range
Default
value
Chan
ge
F9-15
Failure types for the
second time
11: Motor overloading
12: Input default phase
13: Output default phase
14: Modules overheating
15: External failure
16: Communication is abnormal
17: The contactor is abnormal
18: Current detection is abnormal
19: Motor tuning is abnormal
21: The reading and writing of parameters
is abnormal
22: Hardwares of
frequency converter are
abnormal
23: Motor short circuit to the groud
26: The arriving of the running time
27: User-defined failure 1
28: User-defined failure 2
29: The arriving of power-on time
30: Off load
31: PID feedback is missing at overtime
40: Rapid current-limiting is overtime
41: Switch the motor at overtime
42: Speed deviation is too large
43: The motor is
overspeed
-
●
F9-16
Failure types for the
third time (the latest
time)
-
●
F9-17
The frequency when
failures occur for the
third time(the latest
time)
-
-
●
F9-18
The current when
failures occur for the
third time(the latest
time)
-
-
●
F9-19
The Bus voltage for
when failures occur
the third time(the
latest time)
-
-
●
F9-20
The state of input
terminals when
failures occur for the
third time(the latest
time)
-
-
●
F9-21
The state of output
-
-
●