The User Manual of JAC200 Series General Frequency Converter
- 109 -
Set range
0.00Hz
~
Maximum frequency
F8-10
Hopping frequency 2
Default value
0.00Hz
Set range
0.00Hz
~
Maximum frequency
F8-11
Hopping frequency amplitude
Default value
0.00Hz
Set range
0.00
~
Maximum frequency
When the set frequency is within the range of hopping frequency, actual operation frequency shall operate
in the hopping frequency near to the set frequency. Through setting the hopping frequency, the frequency
converter shall be kept away from the resonance point of machinery.
JAC200 can set two hopping frequency points. The hopping frequency function shall be canceled if both
hopping frequencies are set to 0.
Please see Fig. 6-14 diagram for the principle for hopping frequency and hopping frequency amplitude
Fig. 6-14 Hopping frequency diagram
F8-12
Forward/reverse running dead
time
Default value
0.0s
Set range
0.0s
~
3000.0s
In forward/reverse running transient process, the transient time at Output 0Hz is shown in Fig. 6-15: