The User Manual of JAC200 Series General Frequency Converter
- 26 -
Function
code
Name
Set range
Default
value
Chan
ge
F3-14
Voltage digital
setting of VF
separation
0V
~
the rated voltage of motor
0V
☆
F3-15
Voltage acceleration
time of VF
separation
0.0s
~
1000.0s
Note: The above means the time of
variation from 0 V to the rated voltage of
motor
0.0s
☆
F3-16
Voltage deceleration
time of VF
separation
0.0s
~
1000.0s
Note: The above means the time of
variation from 0 V to the rated voltage of
motor
0.0s
☆
F3-17
Selection of VF
separation stop mode
0: Frequency/voltage is independently
decreased to 0
1: Frequency will be decreased continually
after voltage is decreased to 0
0
☆
F3-18
Current limit level
50%
~
200%
150%
★
F3-19
Current limit
selection
0: Disabled
1: Enabled
1
★
F3-20
Current limit gain
0
~
100
20
☆
F3-21
Compensation factor
of speed multiplying
current limit level
50%
~
200%
50%
★
F3-22
Voltage limit
650.0
~
800.0 V
760.0V
★
F3-23
Voltage limit
selection
0: Disabled
1: Enabled
1
★
F3-24
Frequency gain for
voltage limit
0
~
100
30
☆
F3-25
Voltage gain for
voltage limit
0
~
100
30
☆
F3-26
Frequency rise
threshold during
voltage limit
0
~
50 Hz
5Hz
★
Group F4 Input terminals
F4-00
DI1 terminal
function selection
0: No function
1: Forward running FWD or run command
1
★