The User Manual of JAC200 Series General Frequency Converter
- 73 -
to F2-16.
Description of the operation: set this function code as 2, and then press RUN key and the frequency
converter shall do complete tuning.
3: static and complete parameter identification
It is suitable for that without encoder learn for the motor parameter when motor is in static state (at this time
motor may shake slightly, need be careful)
Before doing the static and complete tuning of asynchronous motor, have to set motor type and motor
nameplate parameters from F1-00 to F1-05 correctly. For the static and complete tuning of asynchronous
motor, frequency converter shall get 5 parameters from F1-06 to F1-10.
Group F2 Vector control parameter
Group F2 function code is only valid for vector control, and it is invalid for VF.
F2-00
Proportional gain of speed
loop 1
Default value
30
Set range
1
~
100
F2-01
Integral time of speed loop
1
Default value
0.50s
Set range
0.01s
~
10.00s
F2-02
Switching frequency 1
Default value
5.00Hz
Set range
0.00
~
F2-05
F2-03
Proportional gain of speed
loop 2
Default value
20
Set range
0
~
100
F2-04
Integral time of speed loop
2
Default value
1.00s
Set range
0.01s
~
10.00s
F2-05
Switching frequency 2
Default value
10.00Hz
Set range
F2-02 to maximum output frequency
When frequency converter operates under the different frequency, you can choose different speed loop PI
parameter. When the operation frequency is smaller than switching frequency 1 (F2-02) the speed loop
parameter is F2-00 and F2-01. When operation frequency is bigger than switching frequency 2, speed loop
PI adjustable parameter is F2-03 and F3-04. Speed loop PI parameter between switching frequency 1 and
switching frequency 2 is linear switching for two groups of PI parameters. As shown in the Fig. 6-2: