The User Manual of JAC200 Series General Frequency Converter
- 47 -
Function
code
Name
Set range
Default
value
Chan
ge
FA-21
PID initial value
0.0%
~
100.0%
0.0%
☆
FA-22
Retention time of
PID initial value
0.00
~
650.00s
0.00s
☆
FA-23
The forward
direction maximum
value of two output
deviations
0.00%
~
100.00%
1.00%
☆
FA-24
The reverse direction
maximum value of
two output
deviations
0.00%
~
100.00%
1.00%
☆
FA-25
Integral attribute of
PID
Ones place: integral separation
0: Invalid
1: Valid
Tens place: Whether to stop the integral
after the output arriving at the limit
0: Continue the integral
1: Stop the integral
00
☆
FA-26
Detection value of
PID feedback
missing
0.0%: no judgement of the feedback
missing
0.1%
~
100.0
%
0.0%
☆
FA-27
Detection time of
PID feedback
missing
0.0s
~
20.0s
0.0s
☆
FA-28
Calculation at the
time of shutdown
for PID
0: No calculation at the time of shutdown
1: Calculation at the time of shutdown
0
☆
Group FC Multi-stage instructions, simple PLC
FC-00
Multi-stage
instruction 0
-100.0%
~
100.0%
0.0%
☆
FC-01
Multi-stage
instruction 1
-100.0%
~
100.0%
0.0%
☆
FC-02
Multi-stage
instruction 2
-100.0%
~
100.0%
0.0%
☆
FC-03
Multi-stage
instruction 3
-100.0%
~
100.0%
0.0%
☆
FC-04
Multi-stage
instruction 4
-100.0%
~
100.0%
0.0%
☆
FC-05
Multi-stage
-100.0%
~
100.0%
0.0%
☆