The User Manual of JAC200 Series General Frequency Converter
- 124 -
according to stop mode, after stopping, it shall display Err**.
When we select “continue to operate”: the frequency converter shall continue to operate and display A**,
and the operation frequency shall be set by F9-54.
F9-54
It shall continue to operate
frequency section under the
failure
Default value
0
Set range
0
It shall operate with current operation frequency
1
It shall operate with set frequency
2
It shall operate with upper limit frequency
3
It shall operate with lower limit frequency
4
It shall operate with abnormal standby frequency
F9-55
Abnormal standby frequency
Default value
100.0%
Set range
0.0%
~
100.0% (the maximum frequency)
If there is a failure during the operation of frequency converter, and the handling method of this failure
which was set to be operated continually, the frequency converter shall display A**, and operates with
frequency determined by F9-54.
When we select abnormal standby frequency for operation, the value set by F9-55 shall be the percentage
relative to the maximum frequency.
F9-59
Selection of instantaneous
power failure action
Default value
0
Set value
0
Invalid
1
Deceleration
2
Deceleration for stop
F9-60
The suspension judgment
voltage of instantaneous stop
action
Default value
90.0%
Set range
80.0%
~
100.0%
F9-61
Voltage recovery judgment
time of instantaneous power
failure
Default value
0.50s
Set range
0.00s
~
100.00s
F9-62
The judgment voltage of
instantaneous power failure
action
Default value
80.0%