The User Manual of JAC200 Series General Frequency Converter
- 107 -
Set range
0.0
℃~
100.0
℃
The temperature of inverter module IGBT shall be displayed.
Different types of inverter module IGBT have different overheat protection value.
F7-08
Temporary software version No.
Default value
-
Set range
–
The temporary software version No. of the control panel shall be displayed.
F7-09
Accumulated running time
Default value
0 hour
Set range
0h
~
65535h
The accumulated running time of the frequency converter shall be displayed. When the running time
reaches the set running time F8-17, the multifunctional digital output function (12) shall output ON signal.
F7-10
Product No.
Default value
Set range
Product No. of frequency converter
F7-11
Software version No.
Default value
Set range
Version No. of control panel software
F7-12
Displayed decimal places of load
speed
Default value
1
Set range
0
0 decimal place
1
1 decimal place
2
2 decimal places
3
3 decimal places
It is used to set the displayed decimal places of load speed. The calculation method of load speed is
illustrated below.
If the displayed coefficient F7-06 of load speed is 2.000, and the decimal places F7-12 of load speed are 2
(2 decimal places), when the operation frequency of the frequency converter is 40.00Hz, the load speed
shall be: 40.00*2.000 = 80.00 (2 decimal places displayed)
If the frequency converter is in stop state, the displayed load speed shall be the speed corresponding to set
frequency, i.e. “set load speed”. For example, if the set frequency is equal to 50.00Hz, the load speed in stop
state shall be: 50.00*2.000 = 100.00 (2 decimal places displayed)
F7-13
Accumulated power-on time
Default value
-
Set range
0
~
65535 h
The accumulated power-on time of the frequency convertor since it is delivered from the factory shall be
displayed.
When this time reaches the set power-on time (F8-17), the multifunctional digital output function (24) shall
output ON signal.