The User Manual of JAC200 Series General Frequency Converter
- 88 -
code
F4-11
Terminal command mode
0
Two-line type 1
F4-00
DI1 terminal function selection
1
Forward running(FWD)
F4-01
DI2 terminal function selection
2
Reverse running (REV)
Fig. 6-6 Two-line mode 1
As shown above, in this control mode, when K1 is closed, the frequency converter runs forward. When K2
is closed and runs reversely, and K1 as well as K2 is closed or disconnected simultaneously, the frequency
converter stops running.
1: two-line type 2: In this mode, terminal DI1 functions as operation-enabled terminal, while terminal DI2
can define the running direction.
The function codes are set as follows:
Function
code
Name
Set value
Function description
F4-11
Terminal command mode
1
Two-line type 2
F4-00
Function selection of terminal
DI1
1
Operation-enabled
F4-01
Function selection of terminal
DI2
2
Forward and reverse
running directions
Fig. 6-7 Two-line mode 2
As shown above, in this control mode, when K1 is closed, the frequency converter runs forward with K2
disconnected and runs reversely with K2 closed. When K1 is disconnected, the frequency converter stops