- 65 -
debugging, shall be cautious at the situation that forbid changing the direction of rotation of motor.
F0-10
Maximum
frequency
Default value
50.00Hz
Set range
50.00Hz
~
500.00Hz
When the analog input, multistage instruction etc. of JAC200 is frequency source, and respective 100.0 % is
calibrated as F0-10.
Output-maximum frequency of JAC200 can reach 500Hz. You can select decimal places of frequency
instruction by F0-22 for giving consideration to two indexes that are frequency instruction resolution and
frequent input range.
Note:
Modifying F0-22 can change the frequency resolution of all relative function parameter about frequency.
F0-11
Upper limiting
frequency source
Default value
0
Set range
0
F0-12 setting
1
AI
2
Reserved
3
Key
potentiometer
4
Reserved
5
Communication reference
Define the source of upper limiting frequency. Upper limiting frequency can come from figure setting
(F0-12), analog input
、
Key
potentiometer
or communication reference.
When use analog AI
、
Key
potentiometer
setting or Communication reference, it is similar with main
frequency source. See the introduction of F0-03.
For example when use torque control method at winding control site, you can set upper limiting frequency
by analogue for preventing from material breaking and “galloping” phenomenon. When the frequency
converter operates to upper limiting frequency, frequency converter will keep operating at upper limiting
frequency.
F0-12
Upper limiting
frequency
Default value
50.00Hz
Set range
Lower limiting frequency F0-14-maximum frequency F0-10
Set
upper limiting frequency and the set range is F0-14 -F0-10.
F0-13
Upper limiting
frequency offset
Default value
0.00Hz
Set range
0.00Hz-maximum frequency F0-10
When set the upper limiting frequency source as analogue, F0-13 is the offset of set value. The