The User Manual of JAC200 Series General Frequency Converter
- 84 -
Set
value
Function
Description
22
PID suspending
PID suspends temporarily. Converter maintains the current output
frequency and no longer conducts PID adjustment of frequency
source.
23
PLC state reset
PLC suspends during the execution process. When operating
again, the converter can return to the original state of simple PLC
through the terminal.
24
Swing
frequency
suspending
Converter output by center frequency. Swing frequency function
suspends temporarily.
25
Reserved
Reserved.
26
Counter resetting
Register state conducts reset processing.
27
Length count input
The input terminal of length count.
28
Length reset
Length reset
29
Torque
control
prohibition
The converter is forbidden to conduct torque control. Converter
assesses into speed control mode.
30
Reserved
Reserved
31
Reserved
Reserved
32
Immediate DC braking
When the terminal is valid, the converter switches directly into
DC braking state.
33
External
failure
normally closed input
When external failure normally closed signal was sent into the
converter, the converter sends Failure ERR15 and stop.
34
Frequency modification
prohibition
If the function is set to be valid, when the frequency changes,
converter will not respond the modification of the frequency,
until the state of the terminal is valid.
35
PID
effect
direction
reverse
When the terminal is valid, the direction of the effect of the PID
is opposite to the direction which is set by FA-03.
36
External stop terminal 1
When the keyboard is controlled, the terminal can be used to stop
converter, which can be treated as the function of STOP key in
the keyboard.
37
Control
command
switch terminal 2
Control command switch terminal 2 is used in the switch between
the terminal control and communication control. If the command
source selects to be controlled by the terminal, the system
switches into communication control when the terminal is valid.
Vice versa.
38
PID
integration
suspending
When terminal is valid, adjust function of the integration of PID
suspends, while the proportion adjusting of PID and differential
adjusting function are still valid.
39
The
switch
between
frequency source X and
If the terminal is valid, the frequency source X will be instead by
presetting frequency (F0-08).