The User Manual of JAC200 Series General Frequency Converter
- 116 -
duration exceeds the lagged time of over-current point test, the multifunctional DO of the frequency
converter shall output ON signal. Fig. 6-22 is the output current over limit function diagram.
Fig. 6-22 Output current over limit test diagram
F8-38
Arbitrarily arriving current 1
Default value
100.0%
Set range
0.0%
~
300.0% (Rated current of motor)
F8-39
Arbitrarily arriving current 1
width
Default value
0.0%
Set range
0.0%
~
300.0% (Rated current of motor)
F8-40
Arbitrarily arriving current 2
Default value
100.0%
Set range
0.0%
~
300.0% (Rated current of motor)
F8-41
Arbitrarily arriving current 2
width
Default value
0.0%
Set range
0.0%
~
300.0% (Rated current of motor)
When the output frequency of the frequency converter is within positive/negative detected range of
arbitrarily arriving current, multifunctional DO shall output ON signal. JAC200 provides two groups of
current arrival at any time and detected width parameter. Fig. 6-23 is the function diagram.