The User Manual of JAC200 Series General Frequency Converter
- 87 -
switching among different set values.
Attached Table 2 Function description of the selection terminals of the acceleration /deceleration time
Terminal 2
Terminal 1
Selection of acceleration
/deceleration time
Corresponding
parameter
OFF
OFF
Acceleration time 1
F0-17
、
F0-18
OFF
ON
Acceleration time 2
F8-03
、
F8-04
ON
OFF
Acceleration time 3
F8-05
、
F8-06
ON
ON
Acceleration time 4
F8-07
、
F8-08
Attached Table 3 Description of the functions of motor selection terminal
Terminal 2
Terminal 1
Selection of acceleration
/deceleration time
Corresponding
parameter
OFF
OFF
Motor 1
Group F1, F2
OFF
ON
Motor 2
Group A2
ON
OFF
Motor 3
Group A3
ON
ON
Motor 4
Group A4
F4-10
DI filtering time
Default value
0.010s
Set range
0.000s
~
1.000s
Set the software filtering time of DI terminal state. If the input terminals in application are susceptible
to
interference and cause malfunction, the parameter can be increased to improve the anti-jamming ability. But
the increase of filtering time can slow the response of DI terminal.
F4-11
Terminal command mode
Default value
0
Set range
0
Two-line type 1
1
Two-line type 2
2
Three-line type 1
3
Three-line type 2
The parameter defines four different operation modes of the frequency converter controlled by external
terminals.
Note: For the sake of clarity, randomly select multifunctional input terminals DI1, DI2, and DI3 from DID
to DI10 as external terminals. Namely, select the functions of terminals DI1, DI2, and DI3 by setting the
values of F4-00 to F4-02. See the set ranges of F4-00 to F4-09 for the detailed function definition.
0: two-line type 1: This is the most frequently used two-line type, and the forward running and reverse
running of the motor are decided by terminals DI1, DI2.
The function codes are set as follows:
Function
Name
Set value
Function description