The User Manual of JAC200 Series General Frequency Converter
- 117 -
Fig. 6-23 Arbitrarily arriving frequency test diagram
F8-42
Timing function selection
Default value
0
Set range
0
Invalid
1
Valid
F8-43
Timing running time
selection
Default value
0
Set range
0
F8-44 setting
1
AI
2
Reserved
3
Key
potentiometer
Analog input range 100% corresponding to F8-44
F8-44
Timing running time
selection
Default value
0.0Min
Set range
0.0Min
~
6500.0Min
The paramters group is used to complete the timing operation function of the frequency converter.
When F8-42 timing function selection is valid, Timing shall start when the frequency converter is started.
The frequency converter shall stop automatically when set timing running time is reached. Meanwhile, the
multifunctional DO shall output ON signal.
Timing shall start from 0 each time when the frequency converter is started, and the residual timing running
time can be checked through U0-20.
The timing running time shall be set by F8-43 and F8-44 in minutes.
F8-45
Lower limit of AI input voltage
protection value
Default value
3.10V
Set range
0.00V
~
F8-46
F8-46
Upper limit of AI input voltage
protection value
Default value
6.80V
Set range
F8-45
~
10.00V