The User Manual of JAC200 Series General Frequency Converter
- 135 -
0
No power-down memory
1
Power-down memory
Tens place
Stop memory selection
0
No stop memory
1
Stop memory
The power-down memory of PLC refers to the operation stage and operation frequency before the
frequency converter powers down and when it powers on next time, it can be continued to operate from the
memory stage. If “No memory” is selected, PLC process shall be restarted when the frequency converter
powers-on.
PLC stop memory refers to the last operation stage and operation frequency record before the frequency
converter stops and when it operates next time, PLC stop memory can be continued to operate. If “No
memory” is selected, PLC shall be restarted when frequency converter starts.
FC-18
Stage 0 operation time of Simple
PLC
Default value
0.0s(h)
Set range
0.0s(h)
~
6553.5s(h)
FC-19
Stage 0 deceleration time of simple
PLC
Default value
0
Set range
0
~
3
FC-20
Stage 1 running time of simple PLC
Default value
0.0s(h)
Set range
0.0s(h)
~
6553.5s(h)
FC-21
Stage 1 acceleration time and
deceleration time of simple PLC
Default value
0
Set range
0
~
3
FC-22
Stage 2 running time of simple PLC
Default value
0.0s(h)
Set range
0.0s(h)
~
6553.5s(h)
FC-23
Stage 2 acceleration time and
deceleration time of simple PLC
Default value
0
Set range
0
~
3
FC-24
Stage 3 running time of PLC
Default value
0.0s(h)
Set range
0.0s(h)
~
6553.5s(h)
FC-25
Stage 3 acceleration time and
deceleration time of simple PLC
Default value
0
Set range
0
~
3
FC-26
Stage 4 running time of simple PLC
Default value
0.0s(h)
Set range
0.0s(h)
~
6553.5s(h)
FC-27
Stage 4 acceleration time and
deceleration time of simple PLC
Default value
0
Set range
0
~
3