- 75 -
F2-09
Torque upper limiting source under speed
control mode
Default
value
0
Set range
0
F2-10
1
AI
2
Reserved
3
Key
potentiometer
4
Reserved
5
Communication reference
6
Reserved
7
Resrved
F2-10
Figure setting of torque upper limit under
speed control mode
Default
value
150.0%
Set range
0.0%
~
200.0%
Under the speed control mode, the maximum value of frequency converter output is controlled by torque
upper limiting source.
F2-09 is used to choose the set source of torque upper limit. When set through analogue,
Key
potentiometer
and communication, 100% of corresponding setting correspond F2-10, but 100% of F2-10 is
rated torque of frequency converter.
AI,
Key
potentiometer
setting see the relevant introduction of group F4 curve A1 (select each curve
through F4-27)
.
Select it as Communication reference, write in data from -100.00% to 100.00% through address by upper
computer, where, 100.00% correspond F2-10.
F2-13
Proportional gain of
excitation adjustment
Default value
2000
Set range
0
~
60000
F2-14
Integral gain of excitation
adjustment
Default value
1300
Set range
0
~
60000
F2-15
Integral gain of torque
adjustment
Default value
2000
Set range
0
~
60000
F2-16
Integral gain of torque
adjustment
Default value
1300
Set range
0
~
60000
Parameter of vector control current loop PI adjustment, this parameter can be got automatically after
complete tuning of asynchronous motor or no-load tuning of synchronous motor, and need not be modified.