The User Manual of JAC200 Series General Frequency Converter
- 170 -
Password address
Input password content
1F00H
*****
Data output terminal control: (write only)
Command address
Command content
2001H
BIT0: DO1 output control
BIT1: DO2 input control
BIT2: RELAY1 output control
BIT3: RELAY2 output control
BIT4: FMR output control
Analog output AO1 control: (write only)
Command address
Command content
2002H
0 ~7FFF indicates 0%~100%
Analog output AO2 control: (write only)
Command address
Command content
2003H
0 ~7FFF indicates 0%~100%
PULSE output control: (write only)
Command address
Command content
2004H
0 ~7FFF indicates 0%~100%
Frequency converter failure description:
Frequency converter
failure address
Frequency converter failure
8000H
0000: failure free
0001: reserve
0002: acceleration overcurrent
0003: deceleration overcurrent
0004: constant speed overcurrent
0005: acceleration overvoltage
0006: deceleration overvoltage
0007: constant speed overvoltage
0008: buffer resistance overload
failure
0009: undervoltage failure
000A:
frequency
converter
0015: parameter read-write abnormal
0016: frequency converter hardware failure
0017: motor short circuit to earth failure
0018: reserved
0019: reserved
001A: running time arrival
001B: user defined Failure 1
001C: user defined Failure 2
001D: power-on time arrival
001E: off-loading
001F: PID feedback loss when running
0028: fast current limit timeout failure