The User Manual of JAC200 Series General Frequency Converter
- 134 -
Set range
0
When the single operation ends, it stops.
1
When the single operation ends, it keeps final value.
2
Keeping cycling
The function of simple PLC includes two aspects: used as frequency source and used as the power supply of
VF separation.
Fig. 6-31 is the diagram of simple PLC as frequency source. When simple PLC is used as frequency source,
the positive and negative values of FC-00
~
FC-15 determine operation mode and if it is negative value, it
means that the frequency converter can operate in opposite direction.
Fig. 6-31 Simple PLC Diagram
As frequency source, PLC has three operation modes which can not be used if PLC is used as VF separated
power supply, including:
0: When the single operation ends, it stops.
After the frequency converter finishes one cycle, it will stop automatically and it can start when the new
operation order is given
1 When the single operation ends, it keeps final value.
After the frequency converter finishes one single circulation, it keeps the operation frequency and direction
for the last period.
2: Keeping cycling
After the frequency converter finishes one cycle, the next cycle shall be started till stop order is given.
FC-17
The power-down memory selection
for simple PLC
Default value
00
Set range
Ones place
Power-down memory selection