Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
The setting range:0x000~0x1FF
P05.11
Switch filter
time
Set the sample filter time of S1~S4 and HDI terminals. If the
interference is strong, increase the parameter to avoid the
disoperation.
0.000~1.000s
0.010s
○
P05.12
Virtual
terminals
setting
Enable the input function of virtual terminals at the
communication mode.
0:Virtual terminals is invalid
1:MODBUS communication virtual terminals are valid
2:Reserved
0
◎
P05.13
Terminals
control running
mode
Set the operation mode of the terminals control
0:2-wire control 1, comply the enable with the direction. This
mode is widely used. It determines the rotation direction by
the defined FWD and REV terminals command.
1:2-wire control 2
;
Separate the enable from the direction.
FWD defined by this mode is the enabling ones. The
direction depends on the state of the defined REV.
2:3-wire control 1; Sin is the enabling terminal on this mode,
and the running command is caused by FWD and the
0
◎