Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P01.11
DC braking
current
caused by DC braking at high speed.
DC braking current
:
The value of P01.11 is the percentage
of rated current of inverter. The bigger the DC braking current
is, the greater the braking torque is.
DC braking time: The retention time of DC brake. If the time
is 0, the DC brake is invalid. The inverter will stop at the set
deceleration time.
Setting range of P01.09: 0.00~P00.03 (the Max. frequency)
Setting range of P01.10: 0.0~50.0s
Setting range of P01.11: 0.0~150.0%
Setting range of P01.12: 0.0~50.0s
0.0%
○
P01.12
DC braking
time
0.0s
○
P01.13
Dead time of
FWD/REV
rotation
During the procedure of switching FWD/REV rotation, set the
threshold by P01.14, which is as the table below:
Setting range: 0.0~3600.0s
0.0s
○